Пресс-релиз популярных книг
.
Авторы: 111 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
Книги: 164 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
На сайте 111 авторов, 92 книг, 72 статей, 5913 глав.
15.2 Vibration Exciters
Vibration experimentation may require an external exciter to generate the necessary vibration. This is the
case in controlled experiments such as product testing where a specified level of vibration is applied to the
test object and the resulting response is monitored. A variety of vibration exciters are available, with
different capabilities and principles of operation.
Three basic types of vibration exciters (shakers) are widely used: hydraulic shakers, inertial shakers,
and electromagnetic shakers. The operation-capability ranges of typical exciters in these three categories
are summarized in Table 15.1. Stroke, or maximum displacement, is the largest displacement the exciter
is capable of imparting onto a test object whose weight is assumed to be within its design load limit.
Maximum velocity and acceleration are similarly defined. Maximum force is the largest force that could
be applied by the shaker to a test object of acceptable weight (one within the design load). The values
given in Table 15.1 should be interpreted with caution. Maximum displacement is achieved only at very
low frequencies. The achievement of maximum velocity corresponds to intermediate frequencies in the
operating frequency range of the shaker. Maximum acceleration and force ratings are usually achieved at
high frequencies. It is not feasible, for example, to operate a vibration exciter at its maximum
displacement and its maximum acceleration simultaneously.
Consider a loaded exciter that is executing harmonic motion. Its displacement is given by
x ¼ s sin vt ð15:1Þ
in which s is the displacement amplitude (or stroke). Corresponding velocity and acceleration are
x_ ¼ sv cos vt ð15:2Þ
x€ ¼ 2sv2sin vt ð15:3Þ
Signal
Modification
System
Test
Object
Control
System
Vibration
Exciter (Shaker)
System
FIGURE 15.2 Interactions between major subsystems
of an experimental vibration system.
Vibration Instrumentation 15-3
© 2005 by Taylor & Francis Group, LLC
If the velocity amplitude is denoted by v and the acceleration amplitude by a, it follows from Equation
15.2 and Equation 15.3 that
v ¼ vs ð15:4Þ
and
a ¼ vv ð15:5Þ
Box 15.1
VIBRATION INSTRUMENTATION
Vibration Testing Applications for Products:
* Design and Development
* Production Screening and Quality Assessment
* Utilization and Qualification for Special Applications
Testing Instrumentation:
* Exciter (excites the test object)
* Controller (controls the exciter for accurate excitation)
* Sensors and Transducers (measure excitations and responses and provide excitation error
signals to controller)
* Signal Conditioning (converts signals to appropriate form)
* Recording and Display (perform processing, storage, and documentation)
Exciters:
* Shakers
1. Electrodynamic (high bandwidth, moderate power, complex and multifrequency
excitations)
2. Hydraulic (moderate to high bandwidth, high power, complex and multifrequency
excitations)
3. Inertial (low bandwidth, low power, single-frequency harmonic excitations)
* Transient/Initial Condition
1. Hammers (impulsive, bump tests)
2. Cable Release (step excitations)
3. Drop (impulsive)
Signal Conditioning:
* Filters Amplifiers
* Amplifiers
* Modulators/Demodulators
* ADC/DAC
Sensors:
* Motion (displacement, velocity, acceleration)
* Force (strain, torque)
15-4 Vibration and Shock Handbook
© 2005 by Taylor & Francis Group, LLC
TABLE 15.1 Typical Operation-Capability Ranges for Various Shaker Types
Shaker Type Typical Operational Capabilities
Frequency Maximum Displacement
(Stroke)
Maximum
Velocity
Maximum
Acceleration
Maximum
Force
Excitation
Waveform
Hydraulic
(electrohydraulic)
Low
(0.1 – 500 Hz)
High (20 in; 50 cm) Intermediate
(50 in/sec;
125 cm/sec)
Intermediate
(20 g)
High (100,000 lbf;
450,000 N)
Average flexibility (simple
to complex and random)
Inertial
(counter-rotating mass)
Intermediate
(2 – 50 Hz)
Low (1 in; 2.5 cm) Intermediate
(50 in/sec;
125 cm/sec)
Intermediate
(20 g)
Intermediate
(1,000 lbf; 4,500 N)
Sinusoidal only
Electromagnetic
(electrodynamic)
High
(2 – 10,000 Hz)
Low (1 in; 2.5 cm) Intermediate
(50 in/sec;
125 cm/sec)
High (100 g) Low to intermediate
(450 lbf; 2,000 N)
High flexibility and accuracy
(simple to complex and
random)
Vibration Instrumentation 15-5
© 2005 by Taylor & Francis Group, LLC
An idealized performance curve of a shaker
has a constant displacement – amplitude region, a
constant velocity – amplitude region, and a constant
acceleration – amplitude region for low,
intermediate, and high frequencies, respectively,
in the operating frequency range. Such an ideal
performance curve is shown in Figure 15.3(a) on a
frequency – velocity plane. Logarithmic axes are
used. In practice, typical shaker performance
curves would be fairly smooth yet nonlinear,
curves, similar to those shown in Figure 15.3(b).
As the mass increases, the performance curve
compresses. Note that the acceleration limit of a
shaker depends on the mass of the test object
(load). Full load corresponds to the heaviest object
that could be tested. The “no load” condition
corresponds to a shaker without a test object. To
standardize the performance curves, they are
usually defined at the rated load of the shaker. A
performance curve in the frequency – velocity
plane may be converted to a curve in the
frequency – acceleration plane simply by increasing
the slope of the curve by a unit magnitude (i.e.,
20 db/decade).
Several general observations can be made from
Equation 15.4 and Equation 15.5. In the constantpeak
displacement region of the performance
curve, the peak velocity increases proportionally
with the excitation frequency, and the peak
acceleration increases with the square of the excitation frequency. In the constant-peak velocity region,
the peak displacement varies inversely with the excitation frequency, and the peak acceleration increases
proportionately. In the constant-peak acceleration region, the peak displacement varies inversely with the
square of the excitation frequency, and the peak velocity varies inversely with the excitation frequency.
This further explains why rated stroke, maximum velocity, and maximum acceleration values are not
simultaneously realized.
15.2.1 Shaker Selection
Vibration testing is accomplished by applying a specified excitation to the test package, using a shaker
apparatus, and monitoring the response of the test object. Test excitation may be represented by its
response spectrum. The test requires that the response spectrum of the actual excitation, known as the
test response spectrum (TRS), envelops the response spectrum specified for the particular test, known as
the required response spectrum (RRS).
A major step in the planning of any vibration testing program is the selection of a proper shaker
(exciter) system for a given test package. The three specifications that are of primary importance in
selecting a shaker are the force rating, the power rating, and the stroke (maximum displacement) rating.
Force and power ratings are particularly useful in moderate to high frequency excitations and the stroke
rating is the determining factor for low frequency excitations. In this section, a procedure is given to
determine conservative estimates for these parameters in a specified test for a given test package.
Frequency domain considerations are used here.
StrokeLimit
Max.
Acceleration
Max.
Velocity
Peak Velocity (cm/s)
0.1 1 10 100
Full
Load
No
Load
(a) Frequency (Hz)
Peak Velocity (cm/s)
100
10
1
100
10
1
0.1 1 10 100
Full
Load
No
Load
(b) Frequency (Hz)
FIGURE 15.3 Performance curve of a vibration exciter
in the frequency – velocity plane (log): (a) ideal; (b)
typical.
15-6 Vibration and Shock Handbook
© 2005 by Taylor & Francis Group, LLC
15.2.1.1 Force Rating
In the frequency domain, the (complex) force at the exciter (shaker) head is given by
F ¼ mHðvÞasðvÞ ð15:6Þ
in which v is the excitation frequency variable, m is the total mass of the test package including
mounting fixture and attachments, asðvÞ is the Fourier spectrum of the support-location (exciter head)
acceleration, and H(v) is frequency response function that takes into account the flexibility and
damping effects (dynamics) of the test package apart from its inertia. In the simplified case where the
test package can be represented by a simple oscillator of natural frequency vn and damping ratio by zt ;
this function becomes
HðvÞ ¼ {1 þ 2jztv=vn}={1 2 ðv=vnÞ2 þ 2jztv=vn} ð15:7Þ
in which j ¼
ffiffiffiffi
21 p : This approximation is adequate for most practical purposes. The static weight of the
test object is not included in Equation 15.6. Most heavy-duty shakers, which are typically hydraulic,
have static load support systems such as pneumatic cushion arrangements that can exactly balance the
dead load. The exciter provides only the dynamic force. In cases where shaker directly supports the
gravity load, in the vertical test configuration Equation 15.6 should be modified by adding a term to
represent this weight.
A common practice in vibration test applications is to specify the excitation signal by its response
spectrum. This is simply the peak response of a simple oscillator expressed as a function of its natural
frequency when its support location is excited by the specified signal. Clearly, the damping of the simple
oscillator is an added parameter in a response spectrum specification. Typical damping ratios ðzr Þ used in
response spectra specifications are less than 0.1 (or 10%). It follows that an approximate relationship
between the Fourier spectrum of the support acceleration and its response spectrum is
as ¼ 2jzr ar ðvÞ ð15:8Þ
The magnitude lar ðvÞl is the response spectrum.
Equation 15.8 substituted into Equation 15.6 gives
F ¼ mHðvÞ2jzr ar ðvÞ ð15:9Þ
In view of Equation 15.7, for test packages having low damping the peak value of H(v) is
approximately 1=ð2jzt Þ; this should be used in computing the force rating if the test package has a
resonance within the frequency range of testing. On the other hand, if the test package is assumed to be
rigid, then HðvÞ ø 1: A conservative estimate for the force rating is
Fmax ¼ mðzr =zt Þlar ðvÞlmax ð15:10Þ
It should be noted that lar ðvÞlmax is the peak value of the specified (required) response spectrum (RRS)
for acceleration.
15.2.1.2 Power Rating
The exciter head does not develop its maximum force when driven at maximum velocity. Output power
is determined by using
p ¼ Re½FvsðvÞ ð15:11Þ
in which vsðvÞ is the Fourier spectrum of the exciter velocity, and Re [ ] denotes the real part of a complex
function. Note that as ¼ jvvs: Substituting Equation 15.6 and Equation 15.8 into Equation 15.11 gives
p ¼ ð4mz2r
=vÞRe½jHðvÞa2r
ðvÞ ð15:12Þ
It follows that a conservative estimate for the power rating is
pmax ¼ 2mðz2r
=zt Þ½lar ðvÞl2=vmax ð15:13Þ
Vibration Instrumentation 15-7
© 2005 by Taylor & Francis Group, LLC
Representative segments of typical acceleration RRS curves have slope n, as given by
a ¼ k1vn ð15:14Þ It should be clear from Equation 15.13 that the maximum output power is given by
pmax ¼ k2v2n21 ð15:15Þ
This is an increasing function for n . 1=2 and a decreasing function for n , 1=2: It follows that the power
rating corresponds to the highest point of contact between the acceleration RRS curve and a line of slope
equal to 1/2. A similar relationship may be derived if velocity RRS curves (having slopes n 2 1) are used.
15.2.1.3 Stroke Rating
From Equation 15.8, it should be clear that the Fourier spectrum, xs, of the exciter displacement time
history can be expressed as
xs ¼ 2zr ar ðvÞ=jv2 ð15:16Þ
An estimate for stroke rating is
xmax ¼ 2zr ½lar ðvÞl=v2max ð15:17Þ
This is of the form
xmax ¼ kvn22 ð15:18Þ
It follows that the stroke rating corresponds to the highest point of contact between the acceleration
RRS curve and a line of slope equal to two.
Example 15.1
A test package of overall mass 100 kg is to be
subjected to dynamic excitation represented by the
acceleration RRS (at 5% damping) as shown in
Figure 15.4. The estimated damping of the test
package is 7%. The test package is known to have a
resonance within the frequency range of the
specified test. Determine the exciter specifications
for the test.
Solution
From the development presented in the previous
section, it is clear that the point F (or P) in
Figure 15.4 corresponds to the force and output
power ratings, and the point S corresponds to
the stroke rating. The co-ordinates of these
critical points are F; P ¼ ð4:2 Hz; 4:0 gÞ; and S ¼ ð0:8 Hz; 0:75 gÞ: Equation 15.10 gives the force
rating as
Fmax ¼ 100 £ ð0:05=0:07Þ £ 4:0 £ 9:81 N ¼ 2803 N
Equation 15.13 gives the power rating as
pmax ¼ 2 £ 100 £ ð0:052=0:07Þ £ ½ð4:0 £ 9:81Þ2=4:2 £ 2pwatts ¼ 417 W
Equation 15.17 gives the stroke rating as
xmax ¼ 2 £ 0:05 £ ½ð0:75 £ 9:8Þ=ð0:8 £ 2pÞ2m ¼ 3 cm
Acceleration (g)
Constant Displacement
Constant Velocity
Frequency (Hz)
S
F,P
0.1
0.1
1.0 10 100
1.0
10
FIGURE 15.4 Test excitation specified by an acceleration
RRS (5% damping).
15-8 Vibration and Shock Handbook
© 2005 by Taylor & Francis Group, LLC
15.2.1.4 Hydraulic Shakers
A typical hydraulic shaker consists of a piston-cylinder arrangement (also called a ram), a servo-valve, a
fluid pump, and a driving electric motor. Hydraulic fluid (oil) is pressurized (typical operating pressure:
4000 psi) and pumped into the cylinder through a servo-valve by means of a pump that is driven by an
electric motor (typical power, 150 hp). The flow (typical rate: 100 gal/min) that enters the cylinder is
controlled (modulated) by the servo-valve, which, in effect, controls the resulting piston (ram) motion.
A typical servo-valve consists of a two-stage spool valve, which provides a pressure difference and a
controlled (modulated) flow to the piston, which sets it in motion.
The servo-valve itself is moved by means of a linear torque motor, which is driven by the excitationinput
signal (electrical). A primary function of the servo-valve is to provide a stabilizing feedback to the
ram. In this respect, the servo-valve complements the main control system of the test setup. The ram is
coupled to the shaker table by means of a link with some flexibility. The cylinder frame is mounted on the
support foundation with swivel joints. This allows for some angular and lateral misalignment, which
might be caused primarily by test-object dynamics as the table moves.
Two-degree-of-freedom (Two-DoF) testing requires two independent sets of actuators, and three-DoF
testing requires three independent actuator sets. Each independent actuator set can consist of several
actuators operated in parallel, using the same pump and the same excitation-input signal to the torque
motors.
If the test table is directly supported on the vertical actuators, they must withstand the total dead
weight (i.e., the weight of the test table, the test object, the mounting fixtures, and the instrumentation).
This is requirement is usually prevented by providing a pressurized air cushion in the gap between the
test table and the foundation walls. Air should be pressurized so as to balance the total dead weight
exactly (typical required gage pressure: 3 psi).
Figure 15.5(a) shows the basic components of a typical hydraulic shaker. The corresponding
operational block diagram is shown in Figure 15.5(b). It is desirable to locate the actuators in a pit in the
test laboratory so that the test tabletop is flushed with the test laboratory floor under no-load conditions.
This minimizes the effort required to place the test object on the test table. Otherwise, the test object has
to be lifted onto the test table with a forklift. Also, installation of an aircushion to support the system
dead weight is difficult under these circumstances of elevated mounting.
Hydraulic actuators are most suitable for heavy load testing and are widely used in industrial and civil
engineering applications. They can be operated at very low frequencies (almost direct current [DC]), as well
as at intermediate frequencies (see Table 15.1). Large displacements (stroke) are possible at low frequencies.
Hydraulic shakers have the advantage of providing high flexibility of operation during the test; their
capabilities include variable-force and constant-force testing and wide-band random-input testing. The
velocity and acceleration capabilities of hydraulic shakers are moderate. Although any general excitationinput
motion (for example, sine wave, sine beat, wide-band random) can be used in hydraulic shakers,
faithful reproduction of these signals is virtually impossible at high frequencies because of distortion and
higher-order harmonics introduced by the high noise levels that are common in hydraulic systems. This
is only a minor drawback in heavy-duty, intermediate-frequency applications. Dynamic interactions are
reduced through feedback control.
15.2.1.5 Inertial Shakers
In inertial shakers, or “mechanical exciters,” the force that causes the shaker-table motion is generated by
inertia forces (accelerating masses). Counter-rotating-mass inertial shakers are typical in this category.
To understand their principle of operation, consider two equal masses rotating in opposite directions at
the same angular speed v and in the same circle of radius r (see Figure 15.6). This produces a resultant
force equal to 2mv2r cos vt in a fixed direction (the direction of symmetry of the two rotating arms).
Consequently, a sinusoidal force with a frequency of v and an amplitude proportional to v2 is generated.
This reaction force is applied to the shaker table.
Figure 15.7 shows a sketch of a typical counter-rotating-mass inertial shaker. It consists of two identical
rods rotating at the same speed in opposite directions. Each rod has a series of slots in which to
Vibration Instrumentation 15-9
© 2005 by Taylor & Francis Group, LLC
place weights. In this manner, the magnitude of
the eccentric mass can be varied to achieve various
force capabilities. The rods are driven by a
variable-speed electric motor through a gear
mechanism that usually provides several speed
ratios. A speed ratio is selected depending on the
required test-frequency range. The whole system is
symmetrically supported on a carriage that is
directly connected to the test table. The test object
is mounted on the test table. The preferred
mounting configuration is horizontal so that the
excitation force is applied to the test object in a
horizontal direction. In this configuration, there
are no variable gravity moments (weight £
distance to center of gravity) acting on the drive
mechanism. Figure 15.7 shows the vertical configuration.
In dynamic testing of large structures,
the carriage can be mounted directly on the
structure at a location where the excitation force
should be applied. By incorporating two pairs of
counter-rotating masses, it is possible to generate
test moments as well as test forces.
FIGURE 15.5 A typical hydraulic shaker arrangement: (a) schematic diagram; (b) operational block diagram.
m m
2mw2r cos wt
wt
w w
wt
FIGURE 15.6 Principle of operation of a counterrotating-
mass inertial shaker.
15-10 Vibration and Shock Handbook
© 2005 by Taylor & Francis Group, LLC
Reaction-type shakers driven by inertia are widely used for the prototype testing of civil engineering
structures. Their first application dates back to 1935. Inertial shakers are capable of producing
intermediate excitation forces. The force generated is limited by the strength of the carriage frame. The
frequency range of operation and the maximum velocity and acceleration capabilities are also
intermediate for inertial shakers whereas the maximum displacement capability is typically low. A major
limitation of inertial shakers is that their excitation force is exclusively sinusoidal and that the force
amplitude is directly proportional to the square of the excitation frequency. As a result, complex and
random excitation testing, constant-force testing (for example, transmissibility tests and constant-force
sine-sweep tests), and flexibility to vary the force amplitude or the displacement amplitude during a test
are not generally feasible with this type of shakers. Excitation frequency and amplitude can be varied
during testing, however, by incorporating a variable-speed drive for the motor. The sinusoidal excitation
generated by inertial shakers is virtually undistorted, which gives them an advantage over the other types
of shakers when used in sine-dwell and sine-sweep tests. Small portable shakers with low-force capability
are available for use in on-site testing.
15.2.1.6 Electromagnetic Shakers
In electromagnetic shakers or “electrodynamic exciters,” the motion is generated using the principle of
operation of an electric motor. Specifically, the excitation force is produced when a variable excitation
signal (electrical) is passed through a moving coil placed in a magnetic field.
The components of a commercial electromagnetic shaker are shown in Figure 15.8. A steady magnetic
field is generated by a stationary electromagnet that consists of field coils wound on a ferromagnetic base
that is rigidly attached to a protective shell structure. The shaker head has a coil wound around it. When
the excitation electrical signal is passed through this drive coil, the shaker head, which is supported on
flexure mounts, will be set in motion. The shaker head consists of the test table on which the test object
is mounted. Shakers with interchangeable heads are available. The choice of appropriate shaker head is
based on the geometry and mounting features of the test object. The shaker head can be turned to
different angles by means of a swivel joint. In this manner, different directions of excitation (in biaxial
and triaxial testing) can be obtained.
FIGURE 15.7 Sketch of a counter-rotating-mass inertial shaker.
Vibration Instrumentation 15-11
© 2005 by Taylor & Francis Group, LLC
15.2.2 Dynamics of Electromagnetic Shakers
Consider a single axis electromagnetic shaker (Figure 15.8) with a test object having a single natural
frequency of importance within the test frequency range. The dynamic interactions between the shaker
and the test object give rise to two significant natural frequencies (and correspondingly, two significant
resonances). These appear as peaks in the frequency response curve of the test setup. Furthermore, the
natural frequency (resonance) of the test package alone causes a “trough” or depression (antiresonance)
in the frequency response curve of the overall test setup. To explain this characteristic, consider the
dynamic model shown in Figure 15.9. The following mechanical parameters are defined for
Figure 15.9(a): m, k, and b are the mass, stiffness, and equivalent viscous damping constant, respectively,
of the test package, and me, ke, and be are the corresponding parameters of the exciter (shaker). Also, in
the equivalent electrical circuit of the shaker head, as shown in Figure 15.9(b), the following electrical
parameters are defined: Re and Le are the resistance and (leakage) inductance and kb is the back
electromotive force (back emf) of the linear motor. Assuming that the gravitational forces are supported
FIGURE 15.8 Schematic sectional view of a typical electromagnetic shaker, manufactured by Bruel and Kjaer,
Denmark.
15-12 Vibration and Shock Handbook
© 2005 by Taylor & Francis Group, LLC
by the static deflections of the flexible elements, and that the displacements are measured from the static
equilibrium position, we have the following system equations:
Test object: my€ ¼ 2kðy 2 yeÞ 2 bðy_ 2 y_eÞ ð15:19Þ
Shaker head: mey€e ¼ fe þ kðy 2 yeÞ þ bðy_ 2 y_eÞ 2 key 2 bey_e ð15:20Þ
Electrical: Le
die
dt þ Reie þ kb _ye ¼ vðtÞ ð15:21Þ
The electromagnetic force fe generated in the shaker head is a result of the interaction of the magnetic
field generated by the current ie with coil of the moving shaker head and the constant magnetic field
(stator) in which the head coil is located. Here, we have
fe ¼ kbie ð15:22Þ
Note that v(t) is the voltage signal that is applied by the amplifier to the shaker coil, ye is the displacement
of the shaker head, and y is the displacement response of the test package.
It is assumed that kb has consistent electrical and mechanical units (V/m/sec and N/A). Usually,
the electrical time constant of the shaker is quite small compared with the primarily mechanical
time constants of the shaker and the test package. In such cases, the Ledie=dt term in Equation 15.21 may
be neglected. Consequently, the equations from Equation 15.19 through Equation 15.22 may be
expressed in the Laplace (frequency) domain, with the Laplace variable s taking the place of the derivative
d=dt; as
ðms2 þ bs þ kÞy ¼ ðbs þ kÞye ð15:23Þ
FIGURE 15.9 Dynamic models of an electromagnetic shaker and a flexible test package: (a) mechanical model;
(b) electrical model.
Vibration Instrumentation 15-13
© 2005 by Taylor & Francis Group, LLC
½mes2 þ ðb þ beÞs þ ðk þ keÞye ¼ ðbs þ kÞy þ
kb
Re
v 2
k2
bs
Re
ye ð15:24Þ
It follows that the transfer function of the shaker head motion with respect to the excitation voltage is
given by
ye
v ¼
kb
Re
DðsÞ
DdðsÞ ð15:25Þ
where DðsÞ is the characteristic function of the primary dynamics of the test object
DðsÞ ¼ ms2 þ bs þ k ð15:26Þ
and DdðsÞ is the characteristic function of the primary dynamic interactions between the shaker and the
test object
DcðsÞ ¼ mmes4 þ ½mðbe þ b þ boÞ þ mebs3 þ ½mðke þ kÞ þ mek þ bðbe þ boÞs2
þ ½bke þ ðbe þ boÞks þ kke ð15:27Þ
where
bo ¼
k2
b
Re ð15:28Þ
It is clear that under low damping conditions DdðsÞ will produce two resonances as it is fourth order in s,
and similarly DðsÞ will produce one antiresonance (trough) corresponding to the resonance of the test
object. Note that in the frequency domain, s ¼ jv; and hence the frequency response function given by
Equation 15.25, is in fact
ye
v ¼
kb
Rb
DðjvÞ
Dd ðjvÞ ð15:29Þ
The magnitude of this frequency response function for a typical test system is sketched in Figure 15.10.
Note that this curve is for the “open-loop” case where there is no feedback from the shaker controller.
In practice, the shaker controller will be able
to compensate for the resonances and antiresonances
to some degree, depending on its
effectiveness.
The main advantages of electromagnetic
shakers are their high frequency range of
operation, their high degree of operating flexibility,
and the high level of accuracy of the
generated shaker motion. Faithful reproduction
of complex excitations is possible because of the
advanced electronics and control systems used in
this type of shakers. Electromagnetic shakers are
not suitable for heavy-duty applications (large test
objects), however. High test-input accelerations
are possible at high frequencies when electromagnetic
shakers are used, but their displacement and
velocity capabilities are limited to low or
intermediate values (see Table 15.1).
10.0
1.0
1 10 100
Excitation Frequency (Hz)
Antiresonance
Resonance
Shaker Displacement Magnitude
Resonance
1000
FIGURE 15.10 Frequency response curve of a typical
electromagnetic shaker with a test object.
15-14 Vibration and Shock Handbook
© 2005 by Taylor & Francis Group, LLC
15.2.2.1 Transient Exciters
Other varieties of exciters are commonly used in
transient-type vibration testing. In these tests,
either an impulsive force or an initial excitation is
applied to the test object and the resulting
response is monitored. The excitations and the
responses are “transient” in this case. Hammer
test, drop tests, and pluck tests fall into this
category. For example, a hammer test may be
conducted by hitting the object with an instrumented
hammer and then measuring the response
of the object. The hammer has a force sensor at its
tip, as sketched in Figure 15.11. A piezoelectric or
strain-gage type force sensor may be used. More
sophisticated hammers have impedance heads in
place of force sensors. An impedance head
measures force and acceleration simultaneously.
The results of a hammer test will depend on many
factors; for example, the dynamics of the hammer
body, how firmly the hammer is held during the
impact, how quickly the impact is applied, and
whether there are multiple impacts.
Популярные книги
- Старинные занимательные задачи
- Медоносные растения
- Algebratic geometry
- Workbook in Higher Algebra
- Математика Древнего Китая
- Finite element analysis
- Пчеловодство
- Mathematics and art
- Fields and galois theory
- Black Holes
Популярные статьи
- Higher-Order Finite Element Methods
- Электровакуумные приборы
- Riemann zeta functionS
- Универсальная открытая архитектурно-строительная система зданий серии Б1.020.1-71
- Complex Analysis 2002-2003
- Пример расчета прочности елементов, стыков и узлов несущего каркаса здания
- Составы, вещества и материалы для огнезащитыметаллических консрукций и изделий
- CMOS Technology
- Рекомендации по расчету и конструированию сборных железобетонных колонн каркасов зданий серии Б1.020.1-7 с плоскими стыками ВИНСТ
- Советы старого пчеловода