Пресс-релиз популярных книг
.
Авторы: 111 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
Книги: 164 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
На сайте 111 авторов, 92 книг, 72 статей, 5913 глав.
10.7 BLANKING PRESS NOISE
A typical blanking press is a massive machine, with a mass on the order of
125,000 kg (125t or 275,000 lbm or 137.5 tons). The unit in this case study
was mounted on four footings set on heavy concrete piers (Salmon et al.,
1975). The press produced automobile chassis steel sections of 1
4-inch
(6.4 mm) thick steel with a width of approximately 254mm (10 in) and
lengths between 2.4m (8 ft) and 3.0m (10 ft). The normal operation involved
30 strokes per minute.
494 Chapter 10
TABLE 10-1 Transmission Loss for the Muffler Discussed in
Sec. 10.6
Octave band center frequency, Hz
63 125 250 500 1,000 2,000 4,000 8,000
Lp for LA of 85dBA 102 92 85 79 76 75 75 77
TL for LA of 85 dBA — — 8 18 27 31 35 36
TL provided, dB 10 8 12 20 27 32 43 50
Copyright © 2003 Marcel Dekker, Inc.
10.7.1 Analysis
The vertical acceleration levels for the press pier as a function of frequency
in the acoustic frequency range are shown in Fig. 10-10. These values are
peak acceleration levels averaged over an 0.6-second sampling time. The
peak values are less than the maximum acceleration values because of the
averaging over the sampling time.
The sound pressure level spectrum at the operator’s location is shown
in Fig. 10-11. The operator was located approximately 1.2m (4 ft) from the
press. These octave band sound pressure level readings were obtained from
measurements when the press made a single stroke, so the measurements
corresponded to the peak values averaged over an 0.6-second sampling time,
as was the case for the acceleration data. The sound pressure level indication
Case Studies in Noise Control 495
FIGURE 10-10 Vertical acceleration levels referenced to 10 mm=s2 on the support
pier: (1) before and (2) after installation of vibration isolators.
Copyright © 2003 Marcel Dekker, Inc.
on the ‘‘slow’’ setting on the sound level meter was approximately 10 dB
lower than the peak values shown in Fig. 10-11. The A-weighted sound level
calculated from the data in Fig. 10-11 was 105 dBA, whereas the data measured
on the ‘‘slow’’ setting of the sound level meter was 95 dBA before any
noise control procedure was applied. This value corresponds to an allowable
exposure time of 4 hours according to the OSHA criteria.
The estimation of the acoustic energy radiated from a vibrating surface
of complicated shape due to impact loading must generally be carried
out through a numerical analysis (Beranek and Veґ r, 1992). Reduction of the
vibration transmitted from the machine to the foundation will usually result
in some reduction of the noise radiated by the foundation, however.
496 Chapter 10
FIGURE 10-11 Sound pressure level spectrum (peak values averaged over 0.6 second)
for the blanking press noise at the operator’s location: (1) before installation of
the vibration isolators and (2) after installation of the vibration isolators.
Copyright © 2003 Marcel Dekker, Inc.
10.7.2 Control Approach Chosen
Based on the speed of the press and its mass, special vibration isolators were
designed for placement under the four feet of the press. The vertical peak
acceleration levels (averaged over 0.6 seconds) on the pier after the vibration
isolators were installed are shown in Fig. 10-10. There was no large reduction
in the vibration levels in the octave bands from 31.5Hz to 1000 Hz;
however, there was significant attenuation in the octave bands above
1000 Hz.
The sound pressure level spectrum at the operator’s location after the
vibration isolators were installed is shown in Fig. 10-11. The octave band
sound pressure levels actually increased somewhat for the range from
31.5 Hz to 250 Hz; however, the octave band sound pressure level was
reduced in the higher octave bands. Sound in the octave bands from
about 250 Hz to 8000 Hz is more significant, as far as damage to the
human ear, than noise in the lower frequency range, as discussed in Sec.
6.2. The A-weighted peak sound level calculated from the data in Fig. 10-11
was 99 dBA, and the A-weighted rms sound level measured with the ‘‘slow’’
setting on the sound level meter was approximately 89 dBA.
Although the noise generated by the press after vibration isolators
were installed was less than the OSHA limit for 8-hour exposure
(90 dBA), noise radiated by adjacent presses contribute to the operator’s
work noise exposure. These other operational noise sources for the press
would be controlled separately from the vibration isolation.
The impact of the blanking press produces vibration in the floor of the
building and in the press structure. Often the background noise around a
press that has no vibration isolation is a result of induced vibration of the
building structure, which is probably caused by the anchor bolt aftershock.
Vibration isolators can act to reduce the building structure vibration.
10.7.3 Cost
The vibration isolators selected for this problem were not stock or off-theshelf
items, but were specifically designed for this case. The cost of the
isolators was approximately $5000. The cost for in-plant labor to install
the vibration isolators was approximately $3000.
10.7.4 Pitfalls
One of the major problems in using vibration isolators to reduce noise
radiated from a foundation of complicated shape is that the prediction of
the amount of noise reduction is usually quite difficult and/or expensive.
Although some reduction in support-generated noise will be achieved by
Case Studies in Noise Control 497
Copyright © 2003 Marcel Dekker, Inc.
vibration isolation, the actual noise levels are best determined after the
vibration isolators have been installed.
Some degree of vibration isolation is usually recommended for such
items of machinery as presses. The life of the dies is usually increased and
maintenance problems are usually decreased after the machine has been
treated to reduce vibration. Foundation failures, anchor bolt breakage,
and fracture of the press feet are usually significantly reduced by vibration
isolation of the press.
Популярные книги
- Старинные занимательные задачи
- Медоносные растения
- Математика Древнего Китая
- Algebratic geometry
- Workbook in Higher Algebra
- Finite element analysis
- Mathematics and art
- Fields and galois theory
- Пчеловодство
- Black Holes
Популярные статьи
- Higher-Order Finite Element Methods
- Электровакуумные приборы
- Riemann zeta functionS
- Универсальная открытая архитектурно-строительная система зданий серии Б1.020.1-71
- Complex Analysis 2002-2003
- Пример расчета прочности елементов, стыков и узлов несущего каркаса здания
- Составы, вещества и материалы для огнезащитыметаллических консрукций и изделий
- CMOS Technology
- Рекомендации по расчету и конструированию сборных железобетонных колонн каркасов зданий серии Б1.020.1-7 с плоскими стыками ВИНСТ
- Советы старого пчеловода