Пресс-релиз популярных книг
.
Авторы: 111 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
Книги: 164 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
На сайте 111 авторов, 92 книг, 72 статей, 5913 глав.
10.8 NOISE IN A SMALL MEETING ROOM
In a small meeting room in a university building, the noise level was considered
to be somewhat high; however, the main complaint of people using
the room was that there was an ‘‘echo’’ in the room when someone was
speaking. The floor plan for the meeting room is shown in Fig. 10-12. The
sound pressure level spectrumfor the background noise and for the roomin
the original condition with eight people present in the roomis shown in Fig.
10-13. The overall sound pressure level (measured on the C-scale of the
498 Chapter 10
FIGURE 10-12 Meeting room floor plan. The walls are 3.10m (10 ft 2 in) high. The
floor is carpet on concrete, the ceiling is acoustic tile, the walls are plaster on metal
lath, and the cabinet is constructed of 3
4-in (20-mm) thick plywood. The top cabinet
height is 800mm (311
2 in), and the lower cabinet height is 940mm (37 in). The door is
1:20m _ 2:20m high (3 ft 11 in _ 7 ft 2 1
2 in high), with a thickness of 45mm (13
4 in).
The door has a glass insert, 640mm _ 910mm (25 1
8 in _ 35 5
8 in). There are 16 wooden
chairs in the room.
Copyright © 2003 Marcel Dekker, Inc.
sound level meter) and the A-weighted sound levels are presented in Table
10-2.
10.8.1 Analysis
The speech interference level for the meeting roombefore acoustic treatment
was applied may be calculated from the data in Fig. 10-12:
рLSILЮo ј 1
4 р60ю59ю54ю45Ю ј 54:5 or рLSILЮo ј 55dB
According to the data presented in Table 6-4, a SIL of 55dB corresponds to
face-to-face communication with a ‘‘raised voice’’ for both men and women.
Case Studies in Noise Control 499
FIGURE 10-13 Sound pressure level spectrum for the small meeting room:
(1) before installation of the acoustic material on the walls and (2) after installation
of the acoustic material. The background noise level spectrum (3) is also shown
Copyright © 2003 Marcel Dekker, Inc.
there was a need for reduction of the noise level in the room, because the
room was used for meetings of small groups of people.
Because the reverberation noise seemed to be the major problem with
the acoustic environment of the meeting room, the reverberation time was
estimated by using the Fitzroy expression, Eq. (7-35). The total surface area
of the room was So ј 147:1m2 (1583.6 ft2). The total surface area for the
individual surfaces was as follows: (a) side walls, Sx ј 37:20m2 (400.4 ft2);
end walls, Sy ј 38:44m2 (413.8ft2); and floor–ceiling combination, Sz ј 71:48m2 (769.4ft2). The room volume was V ј 110:8m3 (3913 ft3).
The average surface absorption coefficient for the three sets of interior
surfaces in the 500Hz octave band was estimated as follows:
Side walls: _x ј 0:058; Sx=So ј 0:2529
End walls: _y ј 0:060; Sy=So ј 0:2612
Floor–ceiling: _z ј 0:445; Sz=So ј 0:4859
The number of absorption units for 16 wooden chairs in the 500Hz octave
band was estimated as _р_SЮ ј 0:32m2. It was observed that the surface
absorption of the walls of the roomwas much smaller than that for the floor
and ceiling. This characteristic would allow sound waves traveling horizontally
(fromwall to wall) to decay at a slower rate than those waves traveling
vertically (floor to ceiling and back). It was assumed that this phenomenon
was the source of the ‘‘echoes’’ about which people had complained.
Using Eq. (7-35), the number of absorption units, exclusive of the
chairs, was calculated:
1
ao ј _
1
р147:1Ю
р0:2549Ю
lnр1_0:058Ю ю р0:2612Ю
lnр1_0:060Ю ю р0:4859Ю
lnр1_0:445Ю
_ _
1
ao ј _р_4:233_4:221_0:825Ю
р147:1Ю ј 0:06307m_2
ao ј 15:85m2
500 Chapter 10
TABLE 10-2 Sound Pressure Levels for the Background Noise
and the Noise Before and after Acoustic Treatment of the Meeting
Room Shown in Figure 10-12
LA, dBA Lp, dB LSIL, dB
Background noise 35 48 27
Before acoustic treatment of walls 63 65 55
After acoustic treatment of walls 57 62 48
Copyright © 2003 Marcel Dekker, Inc.
The total number of absorption units, including the 16 chairs, was as follows,
according to Eq. (7-36):
a ј 15:85ю0:32 ј 16:17m2
The reverberation time in the 500Hz octave band before acoustic
treatment was applied was found from Eq. (7-34), using the speed of
sound in air at 228C (728F) as 344.4 m/s (1130 ft/sec):
Tr;o ј р55:26Юр110:8Ю
р344:4Юр16:17Ю ј 1:10seconds
This value of reverberation time was in agreement with measurements for
the empty room.
The optimum reverberation time for a conference room was found
from Eq. (7-38), with a ј _0:101 and b ј 0:3070 from Table 7-3.
Tr;opt ј _0:101 ю 0:3070 log10р110:8Ю ј 0:53 seconds
The optimum reverberation time was approximately half that of the room
before acoustic treatment was applied.
To achieve a reverberation time of 0.53 s for the empty room, including
the 16 chairs, the required number of absorption units was calculated as
follows:
a ј р55:26Юр110:8Ю
р344:4Юр0:53Ю ј 33:544m2
The average surface absorption coefficients for the side walls and the
end walls were approximately the same; therefore, the required surface
absorption coefficient was estimated by using the same value for both sets
of surfaces:
So
a _ 0:32 ј р147:1Ю
р33:544 _ 0:32Ю ј 4:428 ј _рSx=SoЮ ю рSy=SoЮ
lnр1 _ _x;yЮ ю 0:825
_lnр1 _ _x;yЮ ј р0:2529 ю 0:2612Ю
р4:428 _ 0:825Ю ј 0:1426
_x;y ј 0:133
If we let x ј fraction of the side-wall surface area covered with acoustic
material and _m ј surface absorption coefficient for the acoustic material,
the following relationship is valid for the absorption coefficient with the
acoustic material applied:
_x;y ј
_xSxр1 _ xЮ ю _mxSx
Sx
(10-12)
Case Studies in Noise Control 501
Copyright © 2003 Marcel Dekker, Inc.
The acoustic material selected was an acoustic foam, 25-mm (1-in) thick,
with a decorative surface coating. The surface absorption coefficient for the
acoustic material in the 500Hz octave band was _m ј 0:51. The fraction of
the side-wall surface area that should be covered with acoustic material was
determined as follows:
x ј
0:133_0:058
0:51_0:058 ј 0:1657
The surface area for both side walls that was to be covered with the
acoustic material was as follows:
Sm;x ј р0:1657Юр37:20Ю ј 6:164m2 р66:35ft2Ю
For each side wall, the covered surface area was р1
2Юр6:164Ю ј 3:082m2
(33.17ft2).
The fraction of the end walls y to be covered with the acoustic material
was calculated in a similar manner:
y ј
0:133_0:060
0:51_0:060 ј 0:1620
Sm;y ј р0:1620Юр38:44Ю ј 6:223m2 р67:03ft2Ю
By using this amount of wall coverage, the reverberation time for the empty
room should be reduced to approximately 0.5 second.
10.8.2 Control Approach Chosen
Because the walls of the roomhad a fairly small value of surface absorption
coefficient, it was decided to cover the side walls with a total of 7.15m2
(77 ft2) of acoustic material, and the end walls were covered with a total of
7.71m2 (83 ft2) of acoustic material.
The acoustic material selected was an acoustic foam, 25-mm (1-in)
thick, with a decorative surface coating. The acoustic material was available
in the form of 305-mm(12-in) squares, and the material was attached to the
plaster wall using an adhesive compatible with the acoustic material. The
squares were distributed over the wall surface in an aesthetically pleasing
pattern (at least, pleasing to the engineers who used the room).
The overall sound pressure level (measured on the C-scale of the sound
level meter) was 62dB (a 3dB reduction) with eight people in the roomafter
the acoustic treatment was applied, as given in Table 10-2. The A-weighted
sound level after the acoustic material was applied was 57 dBA (a reduction
of 6dBA) with eight people in the room. The speech interference level after
the acoustic material was applied was found from the octave band sound
pressure level measurements given in Fig. 10-13. The SIL after acoustic
502 Chapter 10
Copyright © 2003 Marcel Dekker, Inc.
treatment of the room was LSIL ј 48 dB, which corresponded to the situation
in which conversation in a ‘‘normal’’ voice should be possible in the
room.
The reverberation time for the room after the acoustic treatment was
applied was 0.49 seconds, which is slightly lower than the calculated optimum
value. The problem with annoying ‘‘echoes’’ in the conference room
was eliminated by the use of the acoustic treatment, however.
10.8.3 Cost
The cost for the acoustic material was $140 for one carton containing
1.49m2 (16 ft2) of material. Ten cartons were used, for a total cost of
$1400 for the acoustic material. The cost of the adhesive required to attach
the material to the wall was $26, and shipping and handling costs were $49.
The total material cost for the wall treatment of the conference room was
$1475. University maintenance personnel were used to install the acoustic
material, and the resulting labor cost was approximately $385. The corresponding
total cost for the acoustic project was $1860.
10.8.4 Pitfalls
For the type of acoustic treatment used in this application to be most
effective, it was important to distribute the acoustic material over the
walls. The acoustic material was not concentrated in one area on the walls.
It was noted that the steady-state sound pressure level reduction was
modest (about 6 dB total). If a reduction in steady-state sound pressure level
much more than about 8–10 dB were required, noise control measures other
than acoustic treatment of the walls should be considered. In addition, if the
direct sound field were predominant, the acoustic treament of the room
surface would be ineffective in reducing the noise received directly from
the source.
Популярные книги
- Старинные занимательные задачи
- Медоносные растения
- Математика Древнего Китая
- Algebratic geometry
- Workbook in Higher Algebra
- Finite element analysis
- Mathematics and art
- Fields and galois theory
- Пчеловодство
- Black Holes
Популярные статьи
- Higher-Order Finite Element Methods
- Электровакуумные приборы
- Riemann zeta functionS
- Универсальная открытая архитектурно-строительная система зданий серии Б1.020.1-71
- Complex Analysis 2002-2003
- Пример расчета прочности елементов, стыков и узлов несущего каркаса здания
- Составы, вещества и материалы для огнезащитыметаллических консрукций и изделий
- CMOS Technology
- Рекомендации по расчету и конструированию сборных железобетонных колонн каркасов зданий серии Б1.020.1-7 с плоскими стыками ВИНСТ
- Советы старого пчеловода