Пресс-релиз популярных книг
.
Авторы: 111 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
Книги: 164 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
На сайте 111 авторов, 92 книг, 72 статей, 5913 глав.
5.11 AIR DISTRIBUTION SYSTEMNOISE
Noise generated in air distribution systems is one of the concerns in design
of heating, ventilating, and air conditioning (HVAC) systems. Noise is
transmitted from the air-handling unit (fan) into the duct system. Sound
may also be generated as the air flows through elbows, fittings, and the grill
or diffuser at the duct outlet into the room. The location of these components
in an air distribution systemis illustrated in Fig. 5-4. The sound power
level of the noise introduced into the duct by the fan is given by Eq. (5-8).
192 Chapter 5
Copyright © 2003 Marcel Dekker, Inc.
LWрfan outletЮ ј LW _ 3 dB (5-58)
For industrial air distribution systems that utilize high air velocities, the
noise generated by the air flowing through the distribution system is a
particular concern.
Energy transmitted along the duct may be attenuated or dissipated by
the interaction with the duct wall, or acoustic material may be placed inside
the duct to reduce the noise transmission.
5.11.1 Noise Attenuation in Air Distribution
Systems
There are three primary mechanisms responsible for noise attenuation in air
distribution systems:
(a) Acoustic energy is absorbed by interaction with the duct walls.
(b) Acoustic energy is reflected at the open end of the duct.
(c) Acoustic energy is absorbed by elbows and fittings in the system.
Noise Sources 193
FIGURE 5-4 Air distribution system. _LW is the attenuation in the element, and LW
is the noise generation within the element.
Copyright © 2003 Marcel Dekker, Inc.
The attenuation of sound by each of these mechanisms has been correlated
in terms of the change in the sound power level produced by each element in
the HVAC system (ASHRAE, 1991).
At the junction where a duct divides or has side branches or outlets,
the acoustic power moving down the duct is divided at the duct branch. The
acoustic power from the fan into the duct divides in proportion to the ratio
of the total cross-sectional area of all branches leaving the junction to the
specific branch cross-sectional area. The sound power level for the acoustic
energy transmitted to a specific branch is given by the following expression:
LWрith branchЮ ј LW _ 10 log10
_Sj
Si
_ _
(5-59)
If the duct has no external or internal lining material (a ‘‘bare’’ duct),
the attenuation per unit length for the duct is given in Table 5-15. If the duct
is externally insulated, the attenuation is approximately two times that given
in Table 5-15 for the base duct. If the duct is lined internally with an
absorbent material having an acoustic absorption coefficient _, the attenuation
by the lining material may be estimated, as follows:
(a) For 63 Hz _ f _ 2000 Hz:
_LW ј 4:20_1:4рL=DeЮ (5-60)
The quantity De is the equivalent or hydraulic diameter of the duct and L is
the length of the duct section:
De ј 4S=PW (5-61)
The quantity S is the cross-sectional area of the duct and PW is the perimeter
of the duct cross section.
194 Chapter 5
TABLE 5-15 Attenuation per Unit Length in Bare Ducts,
_LW=L, dB/m
De
ј 4S=Pw, ma
Octave band center frequency, Hz
63 125 250 500 1,000 and greater
0.075 0.59 0.59 0.57 0.53 0.47
0.15 0.59 0.57 0.53 0.47 0.37
0.30 0.57 0.53 0.47 0.37 0.23
0.60 0.53 0.47 0.37 0.23 0.16
1.20 0.47 0.37 0.23 0.085 0.084
2.40 0.42 0.29 0.14 0.033 0.033
aS is the cross-sectional area of the duct and Pw is the perimeter
of the duct.
Copyright © 2003 Marcel Dekker, Inc.
(b) For 2000Hz < f < 8000 Hz:
_LW ј 1
2 Ѕ10ю_LWрEq: 5-60Ю_ (5-62)
(c) For f 8000 Hz:
_LW ј 10 dB (5-63)
The attenuation in the 8kHz and higher octave bands is limited to about
10dB because of line-of-sight propagation of sound through the lined
portion of the duct.
The attenuation due to reflection of the acoustic energy at the open
end of the duct is presented in Table 5-16. The data apply for ducts terminating
flush with the wall or ceiling.
The attenuation of elbows in the systemis given in Table 5.17 (circular
duct) and Table 5-18 (rectangular duct). The data presented in the tables are
for unlined ducts. Using acoustic lining before or after the elbow, or both,
will increase the attenuation by 7 dB to 12 dB in the 4 kHz to 8 kHz octave
bands (Faulkner, 1976, p. 404).
5.11.2 Noise Generation in Air Distribution
System Fittings
In addition to attenuation or dissipation of acoustic energy in fittings, flow
energy may also be converted to acoustic energy in the fittings. Flow-
Noise Sources 195
TABLE 5-16 Octave Band Attenuation (dB) Due to Reflection at the Open
End of the Ducta
foD, Hz-m Attenuation, _LW, dB foD, Hz-m Attenuation, _LW, dB
5 20.6 70 3.7
10 15.3 80 3.1
15 12.4 90 2.6
20 10.5 100 2.2
25 9.1 120 1.6
30 8.1 140 1.0
35 7.2 160 0.6
40 6.4 180 0.3
50 5.3 200 and greater 0.0
60 4.4
aD is the inner diameter for a circular duct and D ј S1=2 for a rectangular duct, where S
is the duct cross-sectional area; fo is the octave band center frequency.
Copyright © 2003 Marcel Dekker, Inc.
induced noise generated in elbows may be estimated from the following
expression (Bullock, 1970):
LW ј Fs ю10log10 fo ю10log10 S ю44:4log10 u_54 (5-64)
The quantity fo is the octave band center frequency, Hz; S is the duct crosssectional
area, m2; and u is the velocity of the air upstream of the elbow,
m/s. The spectrum function Fs is given in Table 5-19. The Strouhal number
Ns is defined by the following expression:
196 Chapter 5
TABLE 5-17 Attenuation of Sound by Circular 908 Elbowsa
foD, Hz-m Attenuation, _LW, dB foD, Hz-m Attenuation, _LW, dB
40 or less 0.0 500 2.2
50 0.2 600 2.4
100 0.7 700 2.5
150 1.1 800 2.6
200 1.3 1,000 2.7
250 1.6 1,500 2.8
300 1.8 2,000 2.9
400 2.0 3,000 and greater 3.0
aThe quantity D is the inner diameter of the elbow and fo is the octave band center
frequency.
TABLE 5-18 Attenuation of Sound by Rectangular 908 Elbowsa
foS1=2, Hz-m Attenuation, LW, dB foS1=2, Hz-m Attenuation, _LW, dB
40 or less 0.0 300 6.8
50 0.4 350 6.5
60 1.0 400 5.9
70 1.6 450 5.4
80 2.4 500 5.0
100 3.6 600 4.5
120 4.8 700 4.1
140 5.6 800 3.8
160 6.2 1,000 3.4
200 6.8 1,200 3.2
250 7.0 1,500 or greater 3.0
aThe quantity S is the cross-sectional area of the duct before the elbow and fo is the octave
band center frequency. The data apply to rectangular ducts with aspect ratios between 0.8
and 1.2.
Copyright © 2003 Marcel Dekker, Inc.
NS ј
foD
u
(5-65)
where D ј р4S=_Ю1=2.
The aerodynamic noise generation produced by 908 branch tees has
been correlated in a manner similar to that used for elbows (Bullock, 1970).
The noise generated and transmitted to the side branch, having a crosssectional
area S3, m2, may be estimated from the following expression:
LW ј Fsb ю10log10 fo ю10log10 S3 юLbr _1:5 (5-66)
For the noise generated and transmitted into the main straight branch, use
the area S2 instead of S3 in Eq. (5-66). The spectrum function for branch
tees is given in Table 5-20. The quantity Lbr is calculated fromthe velocity in
the main straight branch of the tee, u2, and the velocity in the side branch of
the tee, u3, where both velocities are expressed in units of m/s:
Lbr ј 10log10р10L2=10 ю10L3=10Ю (5-67)
L2 ј 46log10 u2 _70 (5-68)
L3 ј 23log10 u3 _20 (5-69)
Noise Sources 197
TABLE 5-19 Spectrum Function Fs for Noise Generation in Elbowsa
NS
ј foD=u 908 elbow, without turning vanes 908 elbow, with turning vanes
0.6 79 49
0.8 67 48
1.0 65 47
2 56 45
4 46 42
6 42 40
8 40 38
10 38 37
20 34 33
40 31 27
60 29 22
100 27 14
200 23 0
aThe Strouhal number is NS ј foD=u, where D ј р4S=_Ю1=2; fo is the octave band center
frequency, Hz; and u is the velocity of the air before the elbow, m/s.
Note: Use logarithmic interpolation with this table;
F _ F1
F2 _ F1 ј
log10рNS=NS1Ю
log10рNS2=NS1Ю
Copyright © 2003 Marcel Dekker, Inc.
The attenuation values are subtracted directly from the sound power
level, in decibels, because the attenuation is an exponential function. On the
other hand, the acoustic energy generation in fittings must be combined by
‘‘decibel addition’’ with the existing sound power. The energy or power is
additive, but the decibel values are not directly additive. This procedure is
illustrated in the example at the end of this section.
5.11.3 Noise Generation in Grilles
Most air distribution systems are terminated by grilles or diffusers. Noise is
generated by the flow of air over the grille or diffuser elements. The following
correlation (Beranek and Veґ r, 1992) may be used to estimate the noise
generated in a grille:
LWрgrilleЮ ј 10 ю 10 log10 S ю 30 log10 CD ю 60 log10 u (5-70)
where S is the cross-sectional area, m2; u is the velocity of the air before
entering the grille, m/s; and CD is the dimensionless grille pressure drop
coefficient, defined by the following expression:
_P ј 1
2CD_u2 (5-71)
198 Chapter 5
TABLE 5-20 Spectrum Function Fsb for Noise
Generated in Branch Duct Take-offsa
NS
ј foD=u1 Fsb, dB NS
ј foD=u1 Fsb, dB
1 80 50 42
2 74 100 35
5 64 200 26
10 57 500 11
20 51 1,000 0
aThe Strouhal number is defined by NS ј foD=u1,
where D ј р4S1=_Ю1=2; fo is the octave band center
frequency, Hz; and u1 is the velocity of the air before
the branch, m/s:
" u3
u2 ? u1
Note: Use logarithmic interpolation with this table:
F _ F1
F2 _ F1 ј
log10рNS=NS1Ю
log10рNS2=NS1Ю
Copyright © 2003 Marcel Dekker, Inc.
The quantity _P is the pressure drop across the grille due to the flowing air
and _ is the density of the air. Specific values for the grille pressure drop
coefficient may be obtained from the grille manufacturer. Some representative
values for CD are given in Table 5-21 for various grille configurations.
The sound generated by air flow through a grille is usually broadband
noise; however, some discrete frequency noise, due to vortex shedding from
the solid elements of the grille, is also present. The peak in the grille noise
spectrumfor HVAC systems occurs at a frequency fm given by the following
dimensional relationship:
fm ј 150u рm=sЮ (5-72)
The octave band sound power levels may be obtained from the following
expression:
LWрoctave bandЮ ј LWрgrilleЮ_CFg (5-73)
Values for the conversion factor CFg are given in Table 5-22.
The directivity factor is not unity for acoustic radiation from a grille,
because the sound is not radiated as spherical waves. The value of the
directivity factor is a function of the dimensionless ratio, f рSЮ1=2=c. Values
for the directivity factor Q and the directivity index, DI ј 10log10 Q, are
given in Table 5-23.
Example 5-7. In the air distribution system shown in Fig. 5-5, the ducts
have a square cross section and are uninsulated. There is one elbow in the
Noise Sources 199
TABLE 5-21 Grille Pressure Drop Coefficient,
CD
Grille type CD
Rectangular grille with no dampers:
parallel louvers 2.9
inclined louvers 2.7
Rectangular grille with dampers:
parallel louvers, open damper 4.8
parallel louvers, partially closed damper 7.3
Circular ceiling diffuser 1.59
High side-wall diffuser (rectangular):
zero angle of deflection of exit air 0.73
458 angle of deflection of exit air 1.93
Source: Hubert (1970) and McQuiston and Parker
(1994).
Copyright © 2003 Marcel Dekker, Inc.
600mm (23.6 in) branch duct and one elbow in the 900mm (35.4 in) main
duct. The grille at the duct outlet has parallel louvers and no dampers. The
volumetric flow rate out of the grille (and through the 600mm branch duct)
is 1440 dm3/s (3051 cfm), and the volumetric flow rate in the 900mm main
duct from the fan is 5050 dm3/s (10,680 cfm). The internal fan sound power
level spectrum is given in Table 5-24. The air in the room is at 258C (778F),
at which condition the sonic velocity is 346.1 m/s (1136 ft/sec). Determine
the steady-state sound pressure level in the roomat a distance of 5m(16.4 ft)
directly in front of the grille р_ ј 08Ю.
200 Chapter 5
TABLE 5-22 Conversion Factors CFg to Convert from
the Overall Sound Power Level for Grille Noise to the
Octave Band Sound Power Levels
Octave band center frequency, Hz
fm=16 fm=8a fm=4 fm=2 fm 2fm 4fm 8fm 16fm
CFg, dB 23 17 11 6 5 7 12 18 24
aThe table entry fm=8, for example, refers to the octave band that
includes the frequency fm=8, where fm is given by Eq. (5-73).
TABLE 5-23 Directivity Factor Q and Directivity Index DI
(dB) for a Duct Opening Flush with the Walla
fS1=2=c Qр_ ј 08Ю DI(08), dB Qр_ ј 458Ю DI(458), dB
0.04 2.0 3.0 2.0 3.0
0.06 2.2 3.4 2.0 3.0
0.08 2.5 4.0 2.0 3.1
0.10 2.7 4.3 2.0 3.1
0.20 3.6 5.6 2.2 3.4
0.40 4.6 6.6 2.7 4.3
0.60 5.3 7.2 3.0 4.8
0.80 5.9 7.7 3.2 5.1
1.0 6.3 8.0 3.3 5.2
2.0 7.2 8.6 3.7 5.7
4.0 7.8 8.9 3.9 5.9
1 8.0 9.0 4.0 6.0
aThe quantity S is the opening cross-sectional area and c is the sonic
velocity in the air. The angle _ is the angle between the desired
direction and the normal to the grille opening.
Copyright © 2003 Marcel Dekker, Inc.
Asample calculation for the 125Hz octave band is given in the following
material. The calculations for the other octave bands are summarized in
Table 5-24. The calculation procedure involves beginning with the sound
power level at the duct inlet and proceeding along the duct system to the
outlet grille in each branch. The attenuation values are subtracted, and the
noise generation values are combined by energy addition at each point
where the energy is generated.
The sound power level produced internally at the fan in the 125 Hz
octave band is given as 71dB. The acoustic energy transmitted through the
fan outlet into the duct system is given by Eq. (5-8):
LWрto ductЮ ј 71_3 ј 68 dB
For a square duct рa ј bЮ, the quantity De ј 4S=PWј р4ЮрabЮ=
2рaюbЮ ј a, the side length of the duct cross section. For the 10m long,
900mm square duct, the attenuation is found from Table 5-15:
_LW ј р0:42 dB=mЮр10mЮ ј 4:2dB
The sound power level before the elbow in the main duct is:
LWрaЮ ј 68 _ 4:2 ј 63:8dB
Noise Sources 201
FIGURE 5-5 Diagram for Example 5-7.
Copyright © 2003 Marcel Dekker, Inc.
202 Chapter 5
TABLE 5-24 Solution for Example 5-7
Item
Octave band center frequency, Hz
63 125 250 500 1,000 2,000 4,000 8,000
LW(fan) 73 71 71 69 61 57 54 48
LW(to duct) 70 68 68 66 58 54 51 45
_LW(10m duct) 5.0 4.2 3.0 3.6 1.2 1.2 1.2 1.2
LW
рaЮ before ell 65.0 63.8 65.0 62.4 56.8 52.8 49.8 43.8
NS 10.2 20.4 40.8 81.6 163 326 652 1,304
Fs 37.8 33.9 30.9 27.8 24.2 20.2 16.2 12.2
LW(elbow) 36.1 35.2 35.2 35.1 34.5 33.5 32.6 31.6
LW
рbЮ in ell 65.0 63.8 65.0 62.4 56.8 52.9 49.9 44.1
foD, Hz-m 56.3 112.5 225 450 900 1,800 3,600 7,200
_LW(elbow) 0.8 4.4 6.9 5.4 3.6 3.0 3.0 3.0
LW to tee 64.2 59.4 58.1 57.0 53.2 49.9 46.9 41.1
Fsb 56.9 50.8 44.0 37.1 28.6 18.0 6.8 _4.2
LW(tee) 62.8 59.7 55.9 52.0 46.5 38.9 30.7 22.7
LW in tee 66.6 62.6 60.1 58.2 54.0 50.2 47.0 41.2
_LW(branch) 5.1 5.1 5.1 5.1 5.1 5.1 5.1 5.1
LW(branch) 61.5 57.5 55.0 53.1 48.9 45.1 41.9 36.1
_LW(12m duct) 6.4 5.6 4.4 2.8 1.9 1.9 1.9 1.9
LW before ell 55.1 51.9 50.6 50.3 47.0 43.2 40.0 34.2
NS 10.7 21.2 42.3 84.6 169 339 677 1,354
Fs 37.6 33.7 30.6 27.7 24.0 20.0 16.0 12.0
LW(elbow) 23.9 23.0 22.9 23.0 22.3 21.3 20.3 19.3
LW in elbow 55.1 51.9 50.6 50.3 47.0 43.2 40.0 34.3
foD, Hz-m 37.8 75 150 300 600 1,200 2,400 4,800
_LW(elbow) 0.0 2.0 5.9 6.8 4.5 3.2 3.0 3.0
_LW(reflect.) 6.8 3.4 0.8 0.0 0.0 0.0 0.0 0.0
_Lw(8m duct) 4.2 3.8 3.0 1.8 1.3 1.3 1.3 1.3
Total attenuation 11.0 9.2 9.7 8.6 5.8 4.5 4.3 4.3
LW(before grille) 44.1 42.7 41.9 41.7 41.2 38.7 35.8 30.0
LW(grille) 55.6 55.6 55.6 55.6 55.6 55.6 55.6 55.6
CFg 17 11 6 5 7 12 18 24
LW(grille, octave band) 38.6 44.6 49.6 50.6 48.6 43.6 37.6 31.6
LW to room 45.2 46.8 50.3 51.1 49.3 44.8 39.8 33.9
Copyright © 2003 Marcel Dekker, Inc.
The quantity D for the 900mm main duct is, as follows:
D ј р4S=_Ю1=2 ј Ѕр4Юр0:810Ю=__1=2 ј 1:016m
The velocity of the air before the elbow in the 900mmmain duct is found as
follows:
u ј Qg=S ј р5:040m3=sЮ=р0:810m2Ю ј 6:22m=s
The Strouhal number for the 125Hz octave band is calculated from its
definition:
NS ј foD=u ј р125Юр1:016Ю=р6:22Ю ј 20:4
The corresponding spectrum function is found in Table 5-19:
Fs ј 33:9
The sound power generated by flow noise through the elbow is found from
Eq. (5-64):
LWрelbowЮ ј33:9ю10log10р125Юю10 log10р0:810Ю
ю44:4 log10р6:22Ю_54
LWрelbowЮ ј 33:9ю21:0юр_0:9Юю35:2_54 ј 35:2dB
The total sound power level at the elbow is found as follows:
LWрbЮ ј 10log10р106:38 ю103:52Ю ј 63:8 dB
For a square duct рa ј bЮ, the quantity S1=2 ј рabЮ1=2 ј a, the side
length of the duct cross section. For the 125Hz octave band, the quantity
foS1=2 ј foa ј р125Юр0:900Ю ј 112:5Hz-m. The attenuation for the elbow is
found fromTable 5-18 to be _LW ј 4:4dB. The sound power level fromthe
elbow to the tee is as follows:
LW (to tee) ј 63:8_4:4 ј 59:4dB
The spectrum function for the side-branch energy generation is found
from Table 5-20 at a Strouhal number, NS ј foD=u1 ј 20:4, or Fsb ј 50:8.
The air velocity in the two branches may be determined as follows:
u2 ј Qg2=S2 ј р5:040 _ 1:440Ю=р0:810Ю ј 4:44m=s
u3 ј Qg3=S3 ј р1:440Ю=р0:360Ю ј 4:00m=s
The branch functions given in Eqs. (5-68) and (5-69) may be determined:
L2 ј 46 log10р4:44Ю _ 70 ј _40:2dB
L3 ј 23 log10р4:00Ю _ 20 ј _6:2dB
Noise Sources 203
Copyright © 2003 Marcel Dekker, Inc.
These values may be combined according to Eq. (5-67):
Lbr ј 10log10р10_4:02 ю10_0:62Ю ј _6:2 dB
The acoustic energy generated within the tee in the 125Hz octave band
is determined from Eq. (5-66):
LWрteeЮ ј 50:8ю10 log10р125Юю10log10р0:810Ююр_6:2Ю_1:5
ј 59:7 dB
The acoustic power in the tee is found by combining the energy before the
tee and the energy generated within the tee:
LW (in tee) ј 10log10р105:94 ю105:97Ю ј 62:6 dB
The energy delivered to the 600mm branch duct is found from Eq.
(5-59):
LW _LWрbranchЮ ј 10 log10
0:810ю0:360
0:360
_ _
ј 5:1dB
The sound power level delivered to the 600mm side branch in the 250 Hz
octave band is:
LWрbranchЮ ј 62:6_5:1 ј 57:5dB
The attenuation in the 12m long run of the side branch may be calculated
as follows. The attenuation per unit length is found from Table 5-15,
with De ј 0:600m for the square cross section:
_LWр12 m ductЮ ј р0:47dB=mЮр12mЮ ј 5:6 dB
The sound power level to the elbow in the 125Hz octave band is as follows:
LW (before elbow) ј 57:5_5:6 ј 51:9dB
The energy generated in the elbow in the 600mm duct may be determined
by the same procedure as that for the previous elbow. The quantity D
for the smaller duct is as follows:
D ј р4S=_Ю1=2 ј Ѕр4Юр0:360Ю=__1=2 ј 0:677m
The Strouhal number is calculated from its definition:
NS ј foD=u3 ј р125Юр0:667Ю=р4:00Ю ј 21:2
The spectrum function is found from Table 5-19, Fs ј 33:7. The noise
generated in the elbow is found from Eq. (5-64):
204 Chapter 5
Copyright © 2003 Marcel Dekker, Inc.
LWрelbowЮ ј Fs ю10log10 fo ю10log10 S ю44:4log10 u3 _54
LWрelbowЮ ј33:7ю10log10р125Юю10 log10р0:360Юю44:4 log10р4:00Ю
_54
LWрelbowЮ ј 33:7ю21юр_4:4Юю26:7_54 ј 23:0dB
The sound power level in the elbow in the 600mmbranch run is found
by combining the energy generated and the energy to the elbow:
LW (in elbow) ј 10 log10р105:19 ю102:30Ю ј 51:9dB
It is noted that the noise generated in the smaller elbow is negligible in this
example.
The attenuation in the elbow is found as follows. The quantity
foS1=2 ј р125Юр0:600Ю ј 75 Hz-m. The attenuation of the elbow in the
125Hz octave band is found from Table 5-18, _LWрelbowЮ ј 2:0dB.
The attenuation due to reflection at the open end of the 600mmsquare
duct is found from Table 5-16 at a value foD ј 75Hz-m for the 125 Hz
octave band, _LWрreflectionЮ ј 3:4dB.
The attenuation in the 8m long section of the branch is as follows:
_LWр8m ductЮ ј р0:47dB=mЮр8mЮ ј 3:8dB
The total attenuation from the elbow to the open end of the duct in the
125Hz octave band is found by adding the three contributions (elbow,
straight length, and reflection):
_LWрtotalЮ ј 2:0ю3:4ю3:8 ј 9:2dB
The sound power level before the grille is as follows:
LW (before grille) ј 51:9_9:2 ј 42:7dB
The grille pressure drop coefficient, from Table 5-21, is CD ј 2:9. The
overall power level generated by the flow through the grille may be found
from Eq. (5-70):
LWрgrilleЮ ј 10ю10 log10 S ю30 log10 CD ю60log10 u
LWрgrilleЮ ј 10ю10 log10р0:360Юю30log10р2:9Юю60log10р4:00Ю
LWрgrilleЮ ј 10юр_4:4Юю13:9ю36:1 ј 55:6dB рoverallЮ
The peak frequency of the grille power level spectrum occurs at the following
frequency, according to Eq. (5-72):
fm ј р150Юр4:00Ю ј 600 Hz
This frequency falls in the 500Hz octave band, so the frequency 125 Hz
corresponds to fm=4, and CFg ј 11, from Table 5-22. The sound power
Noise Sources 205
Copyright © 2003 Marcel Dekker, Inc.
level generated by the flow through the grille for the 125Hz octave band is
found from Eq. (5-73):
LWрgrille, octave bandЮ ј 55:6_11 ј 44:6dB (125 Hz octave band)
The sound power level delivered from the grille to the room may be
determined by combining the sound power level before the grille and the
power level generated in the grille:
LW (to room) ј 10log10р104:27 ю104:46Ю ј 46:8dB
This calculation completes the first part of the problem, which is to
determine the sound power level input to the room. Next, let us use this data
to determine the steady-state sound pressure level in the room. We will
continue to present a sample calculation for the 125Hz octave band and
present the results for the other octave bands in Table 5-25.
Values for the room constant in each octave band are given in Table
5-25. The dimensionless parameter needed to determine the directivity factor
for the grille opening is as follows:
foS1=2
c ј р125Юр0:360Ю1=2
р346:1Ю ј 0:217
The directivity factor is found from Table 5-23, Qр_ ј 08Ю ј 3:7.
The second term in Eq. (5-6) may be calculated:
10 log10
4
R ю
Q
4_r2
_ _
ј 10 log10
4
7:1 ю р3:7Ю
р4_Юр5:00Ю2
_ _
ј _2:4dB
206 Chapter 5
TABLE 5-25 Solution for Overall Sound Pressure Level in Example 5-7
Item
Octave band center frequency, Hz
63 125 250 500 1,000 2,000 4,000 8,000
Lw to room 45.2 46.8 50.3 51.1 49.3 44.8 39.8 33.9
R, m2 (given) 4.2 7.1 8.6 11.8 15.1 17.8 19.1 22.0
foS1=2=c 0.109 0.217 0.433 0.867 1.73 3.47 6.93 13.87
Qр_ ј 08Ю 2.8 3.7 4.8 6.0 7.0 7.7 7.9 8.0
10 log10
4
R
ю Q
4_r2
_ _
_0.2 _2.4 _3.2 _4.5 _5.4 _6.0 _6.3 _6.8
Lp, dB 45.1 44.5 47.2 46.7 44.0 38.9 33.6 27.2
Background Lp 55 50 45 40 35 30 28 28
Total Lp, dB 55.4 51.1 49.2 47.5 44.5 39.4 34.7 30.6
Copyright © 2003 Marcel Dekker, Inc.
The sound pressure level in the 125Hz octave band may be found from Eq.
(5-6) for sound propagated indoors:
Lp ј 46:8юр_2:4Юю0:1 ј 44:5 dB
The background sound pressure level in the 125Hz octave band is
given as 50 dB in Table 5-25. The total octave band sound pressure level
may be found by combining the noise from the grille and the background
noise.
Total Lpрoctave bandЮ ј 10 log10р104:45 ю 105:00Ю ј 51:1dB
The overall sound pressure level is found by combining the octave
band sound pressure level values:
LpрoverallЮ ј 10 log10р105:54 ю 105:11 ю_ _ _ю103:06Ю ј 58:2dB
Популярные книги
- Старинные занимательные задачи
- Медоносные растения
- Algebratic geometry
- Workbook in Higher Algebra
- Математика Древнего Китая
- Finite element analysis
- Mathematics and art
- Fields and galois theory
- Пчеловодство
- Black Holes
Популярные статьи
- Higher-Order Finite Element Methods
- Электровакуумные приборы
- Riemann zeta functionS
- Универсальная открытая архитектурно-строительная система зданий серии Б1.020.1-71
- Complex Analysis 2002-2003
- Пример расчета прочности елементов, стыков и узлов несущего каркаса здания
- Составы, вещества и материалы для огнезащитыметаллических консрукций и изделий
- CMOS Technology
- Рекомендации по расчету и конструированию сборных железобетонных колонн каркасов зданий серии Б1.020.1-7 с плоскими стыками ВИНСТ
- Советы старого пчеловода