Пресс-релиз популярных книг
.
Авторы: 111 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
Книги: 164 А Б В Г Д Е Ж З И Й К Л М Н О П Р С Т У Ф Х Ц Ч Ш Щ Э Ю Я
На сайте 111 авторов, 92 книг, 72 статей, 5913 глав.
8.9 PLENUM CHAMBERS
A plenum chamber is similar to a dissipative silencer, but it is also similar
to a small room with a noise source in one wall. The dimensions of the
plenum chamber are usually larger than the wavelength of the sound being
attenuated. In addition, the inlet and outlet of the plenum chamber are
usually not placed on the same axis, which is often the case for dissipative
silencers.
One of the applications for plenum chambers is to smooth out flow
fluctuations and poor velocity distribution after a fan or blower in an air
distribution system, in addition to attenuation of the noise generated by the
fan or blower.
The results of experimental measurements of plenum chamber acoustic
performance are available in the literature (Wells, 1958; Benade, 1968). The
following analysis yields expressions that predict acoustic performance in
good agreement with experimental data for wavelengths smaller than the
dimensions of the chamber. At low frequencies (wavelengths much larger
than the chamber dimensions), the calculated transmission loss may be
5–10 dB smaller than experimental data, i.e., the calculations are ‘‘conservative’’
as far as the noise control situation is concerned. When the ‘‘room
Silencer Design 391
FIGURE 8-20 Schematic of a silencer for automotive applications.
Copyright © 2003 Marcel Dekker, Inc.
constant’’ for the plenum is very large (or the surface absorption coefficient
for the lining approaches unity), the transmission loss for the plenum is
determined primarily by the direct acoustic energy from the inlet to the
outlet.
Let us consider the plenum chamber shown in Fig. 8-22. The acoustic
intensity associated with the inlet energy Win that is radiated directly from
the inlet (area SoЮ to the outlet is given by the following expression:
ID ј
QWin
4_d2 (8-184)
The directivity factor Q ј 2, if the inlet opening is located near the center of
the inlet side of the plenum chamber. If the inlet opening is located near the
top or bottom edge of the inlet side of the plenum chamber, Q ј 4. The
quantity d is the slant distance between the center of the inlet and center of
the outlet opening of the plenum chamber. For the plenum chamber shown
in Fig. 8-22, the distance d is given by the following expression:
d ј ЅрL_hЮ2 юH2_1=2 (8-185)
392 Chapter 8
FIGURE 8-21 Baffle-type or panel-type silencers: (a) in-line panels and (b) staggered
panels with heat-recovery water-filled tubes.
Copyright © 2003 Marcel Dekker, Inc.
The quantity L is the vertical dimension of the plenum chamber (if the
openings are located in the vertical sides of the chamber),H is the horizontal
distance between the inlet and outlet openings, and h is the height (or
diameter, if circular) of the openings.
An alternative arrangement for the inlet and outlet openings for a
plenum chamber is shown in Fig. 8-23. For this case, the angle _ is given
by the following expression:
cos_ ј L1=d (8-186)
The dimension L1 is the distance between the center of the inlet opening and
the chamber side in which the outlet opening is located, and d is the slant
distance between the two openings.
The acoustic energyWout;D associated with the direct sound field at the
outlet is found by multiplying the intensity by the area of the outlet opening
projected in the direction of the inlet opening:
Wout;D ј
QWinSo cos _
4_d2 (8-187)
The angle _ is defined in Fig. 8-22, and is given by the following expression:
cos_ ј H=d (8-188)
The acoustic energy density associated with the reverberant sound field
in the plenum chamber may be determined from Eq. (7-12):
DR ј
4Win
cR
(8-189)
Silencer Design 393
FIGURE 8-22 Configuration for a plenum chamber.
Copyright © 2003 Marcel Dekker, Inc.
The quantity R is the room constant for the plenum chamber:
R ј
S__
1 _ __
(8-190)
The surface area S is the total surface area of the chamber, including the
lined surface area SL and the area of each opening So:
S ј SL ю 2So (8-191)
The average surface absorption coefficient __ may be determined from the
following expression, assuming that the absorption coefficient for the openings
is unity:
__ ј
__LSL ю 2So
S
(8-192)
The sound power at the outlet opening associated with the reverberant
sound field is given by Eq. (7-10):
Wout;R ј 1
4DRcSo ј WinSo=R (8-193)
The total energy leaving the plenum chamber is the sum of the direct
and reverberant components from Eqs (8-187) and (8-193):
Wout ј WinSo
Qcos _
4_d2 ю
1
R
_ _
(8-194)
394 Chapter 8
FIGURE 8-23 Plenum chamber with an alternative location for the outlet.
Copyright © 2003 Marcel Dekker, Inc.
The sound pressure transmission coefficient may be determined from Eq.
(8-194):
at ј
Wout
Win ј
SoQcos _
4_d2 ю
So
R
(8-195)
The transmission loss for the chamber is given by the following expression:
TL ј 10log10р1=atЮ (8-196)
The first term in Eq. (8-194) represents the energy transmitted directly from
the inlet to the outlet opening of the plenum chamber. The second term
represents the energy from the reverberant field within the chamber.
A double-chamber plenum, as shown in Fig. 8-24, may be used to
reduce the effect of the direct sound transmission. If we denote the first or
inlet section by subscript 1 and the second or outlet section by subscript 2,
the sound power transmission coefficient for the double-chamber plenum
may be estimated from Eq. (7-69) with the transmission coefficient of the
opening between the two chambers taken as unity and Sw ј S01:
at ј
Wout
Win ј
So1
R1
So2 Q2 cos _2
4_d2
2 ю
4So2
R2
_ _
(8-197)
The quantities So1 and So2 are the outlet areas for each chamber and R1 and
R2 are the room constants for each chamber, given by Eq. (8-190).
Example 8-12. A plenum chamber has dimensions of 0.800m р31:5inЮ _ 0:800m_1:600m (63.0 in) long. The inlet and outlet ducts have a height of
h ј 300mm (11.8in) and a width of 400mm (15.75in). The inlet and outlet
duct openings are located along the edge of the plenumрQ ј 4Ю, as shown in
Fig. 8-22. The plenum chamber is lined with 1-in thick acoustic foam, the
Silencer Design 395
FIGURE 8-24 Double-chamber plenum.
Copyright © 2003 Marcel Dekker, Inc.
properties of which are given in Appendix D. Determine the transmission
loss for the plenum chamber.
The slant distance between the inlet and outlet openings is as follows:
d2 ј рL_hЮ2 юH2 ј р0:800_0:300Ю2 ю1:6002 ј 2:810m2
d ј 1:676m р5:50ftЮ
The cosine of the angle between the slant distance and the normal to the
outlet opening is as follows:
cos_ ј
H
d ј
1:600
1:676 ј 0:9545 or _ ј 17:358
The areas of the openings and the lined portion of the chamber are as
follows:
So ј р0:300Юр0:400Ю ј 0:120m2 р1:292 ft2Ю
SL ј р2Юр0:800ю0:800Юр1:600Ю ю р2Юр0:800Юр0:800Ю _ р2Юр0:120Ю
SL ј 6:160m2 р66:31ft2Ю
Let us work out the transmission loss for the octave band with a center
frequency of 500 Hz. The surface absorption coefficient for the acoustic
foam at 500Hz is 0.51. The average surface absorption coefficient in the
500Hz octave band for the plenum is found using Eq. (8-192):
__ ј р6:160Юр0:51Ю ю р2Юр0:120Ю
р6:400Ю ј 0:5284
The room constant for the plenum is found from Eq. (8-190):
R ј р6:400Юр0:5284Ю
1_0:5284 ј 7:170m2
The sound power transmission coefficient for the 500Hz octave band
is determined from Eq. (8-195):
at ј р0:120Ю
р7:170Ю ю р4Юр0:9545Юр0:120Ю
р4_Юр1:676Ю2 ј 0:01674ю0:01297 ј 0:02971
The transmission loss for the plenum in the 500Hz octave band is as
follows:
TL ј 10log10р1=0:02971Ю ј 15:3 dB
The calculations may be repeated for the other octave bands. The
results are summarized in Table 8-5.
396 Chapter 8
Copyright © 2003 Marcel Dekker, Inc.
Популярные книги
- Старинные занимательные задачи
- Медоносные растения
- Algebratic geometry
- Workbook in Higher Algebra
- Математика Древнего Китая
- Finite element analysis
- Mathematics and art
- Fields and galois theory
- Пчеловодство
- Black Holes
Популярные статьи
- Higher-Order Finite Element Methods
- Электровакуумные приборы
- Riemann zeta functionS
- Универсальная открытая архитектурно-строительная система зданий серии Б1.020.1-71
- Complex Analysis 2002-2003
- Пример расчета прочности елементов, стыков и узлов несущего каркаса здания
- Составы, вещества и материалы для огнезащитыметаллических консрукций и изделий
- CMOS Technology
- Рекомендации по расчету и конструированию сборных железобетонных колонн каркасов зданий серии Б1.020.1-7 с плоскими стыками ВИНСТ
- Советы старого пчеловода